Permit Number: TC-COM-0226-00222
Parcel: 128010040

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00222
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2026 Commercial Building Standard APPROVED
03/06/2026 Commercial Electrical Standard APPROVED Approved with comments added to the plans.
03/11/2026 Commercial Mechanical Standard APPROVED
03/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/11/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Floor sinks located within the kitchen area or subject to grease waste shall be connected to the grease waste system. (Note: this may be appealed to Pima County RWRD.) Reference: Section 1003.3 (A), IPC 2024, as amended by the City of Tucson.
2. Hand sinks (52) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
3. State the minimum gas pressure required for each appliance by the appliance manufacturer. Reference: Section 402.1, IFGC 2024.
4. Provide natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths (from the meter or regulator to the appliance) on plans. Reference: Section 402.3, IFGC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/06/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0226-00222 (5950 E BROADWAY BL Unit:UNIT 110 TUCSON, AZ 85711)
Outdoor Lighting Review TC-COM-0226-00164 (3401 E GAS RD TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Reference Sheet E2.1, Keyed Notes #5. Festoon lighting is required to meet the requirements of the outdoor lighting code. These string lighting fixtures are typically unshielded and must be included in a site lumen calculation.
a. Option one: remove note and electrical for festoon lighting.
b. Option two: provide Outdoor Lumen Calculations per OLC 102.4, & 104.2, and include the lights as unshielded fixtures.
c. Option three: correct note to indicate that the installation of these festoon lighting fixtures will be done by separate permit in the future. They cannot be installed without permits and calculations.
2. Note on the plans that lighting fixture LI-3 is full cutoff and under a canopy or overhang to qualify for exemption OLC 104.2.1, and 401.2.1(3).
02/26/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0226-00222 (1st Review)
Project: Tenant improvement to an existing, vacant 6,024 s.f. space within an existing shell.
Location: 5950 E BROADWAY BL Unit: UNIT 110
Review Date: 2/26/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering

Site Engineering Comments:
1. It will be required that Sheet 3 (A-1.0) be revised to match the approved site plans associated with the approved development package TD-DEV-0325-00090.

If you have any questions or concerns, please contact Marco Contreras at Marco.contreras@tucsonaz.gov
03/11/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0226-00222 - TD-DEV-0325-00090
5950 E. Broadway Blvd. Unit 110 Tucson, AZ 85711
TI (1st Review)

TRANSMITTAL DATE: 3/11/2026

This site is located in the C-2 zone (UDC 4.7.21). Food Service with Alcoholic Beverage Service is a permitted use.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Sheet 3 (site plan) does not match the approved site plan in the associated Development Package (TD-DEV-0325-00090). Please ensure the trash enclosures and associated parking improvements shown on this site plan are consistent with what was approved in the Development Package.
2. Comment: Additional comments may be forthcoming on the next review based on the proposed use and any applicable use specific standards.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
03/11/2026 Water - PDSD Standard REQUIRES RESUBMIT Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
03/16/2026 Fire New Construction Standard REVIEW COMPLETED
02/19/2026 PDSD Application Completeness Express REVIEW COMPLETED