Permit Number: TC-COM-0226-00222
Parcel: 128010040

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0226-00222
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2026 Site Zoning Standard APPROVED Associated DP (TD-DEV-0325-00090) has been approved.
06/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/09/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Delivering a minimum pressure of 7” WC at the inlet of appliances that require 7” WC is physically impossible if the pressure regulator is set for a discharge of 7” WC. [Second comment: Provide the delivery pressure setting for the existing pressure regulator to ensure a minimum pressure of 7” WG to each appliance.] [Initial comment: State the minimum gas pressure required for each appliance by the appliance manufacturer. Reference: Section 402.1, IFGC 2024.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/05/2026 Addressing Validation REVIEW COMPLETED
06/05/2026 PDSD Application Completeness Express REVIEW COMPLETED