Permit Number: TC-COM-0226-00161
Parcel: 13629003F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0226-00161
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2026 Commercial Building APPROVED
02/11/2026 Site Engineering APPROVED
02/06/2026 Site Zoning APPROVED
02/10/2026 Fire New Construction NOT REQUIRED
02/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/05/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00161 (8155 E POINCIANA DR TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide Electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the EV charging load (Include the EV charger in the load calculations as a continuous use item). NEC 625.42.
2. Where subject to physical damage, conductors, raceways, equipment, and cables shall be protected. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage. Verify EV charging equipment is protected from physical damage or provide tire stops or bollards or other means to protect from car impacts.
3. Provide disconnecting means at the location of the charging equipment, or provide a plaque installed on the charging equipment denoting the location of the disconnecting means, NEC 625.43.
4. Conductors labeled D1, D2 & D3 are undersized. OCPD(Breaker) for copper conductor may not exceed 15A for #14 AWG conductors as required by NEC 240.4(D)(small conductors). Provide minimum #12 AWG CU conductors for this circuit.
5. Update ‘Governing Codes’ to show the currently adopted codes. 2024 ICC and 2023 NEC.
02/05/2026 PDSD Application Completeness Express REVIEW COMPLETED