Permit Number: TC-COM-0226-00158
Parcel: 108193040

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00158
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2026 Commercial Mechanical Standard APPROVED
02/27/2026 Site Zoning Standard APPROVED
03/03/2026 Water - PDSD Standard APPROVED
02/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/12/2026 Site Engineering Standard NOT REQUIRED
03/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/05/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00158
ADDRESS/PARCEL: (4578 N 1ST AV Unit:UNIT 190 TUCSON, AZ 85718)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. Please re-calculate the occupant load for the following spaces:
a. Waiting Area
b. Break Room Area
c. The above should be using 15 sq ft Occupant Load Factor per IBC Table 1004.5.
d. Please correct the Code Analysis reflecting the above recalculation.
e. Correct the Exit Width calculation.
f. Correct the Plumbing Fixture Calculation.
2. Provide Code compliant High Low Drinking Fountain for the public at the Waiting Area. IBC TABLE 2902.1 / ICC A117.1 section 602.
3. Please resubmit.
02/18/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00158 (4578 N 1ST AV Unit:UNIT 190 TUCSON, AZ 85718)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. If the registrant is not a registered electrical engineer, the registrant must be qualified to perform such work per A.A.C. R4-30-302 and the electrical work must be incidental to the work of the registrant’s profession for the project per A.R.S. 32-143. (Incidental is defined as minor electrical work that is a result of the work of the registrant’s profession for the project).
a. The provided scope of work does not meet the definition of ‘incidental’. The electrical sheets must be sealed by an Arizona Registered Electrical Engineer.
2. Provide electrical notes/sheets showing compliance with 2017 NEC Article 517 for health care facilities. Note areas subject to section 517.10(A).
a. This shall include, but not be limited to, any required ‘Essential Electrical Systems’, 517.25, Equipment Grounding, 517.13, ‘Category’ definition of each space, 517.18-19, etc.
03/03/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Revise the hot water piping so that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/03/2026 Fire New Construction Standard REVIEW COMPLETED
02/06/2026 PDSD Application Completeness Express REVIEW COMPLETED