Permit Number: TC-COM-0226-00154
Parcel: 12511251A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00154
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2026 Commercial Electrical Standard APPROVED
03/02/2026 Site Zoning Standard APPROVED
03/02/2026 Water - PDSD Standard APPROVED
02/17/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/12/2026 Site Engineering Standard NOT REQUIRED
03/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/04/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00154
ADDRESS/PARCEL: (615 N ALVERNON WY TUCSON, AZ 85711)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. EGRESS PLAN
a. I notice that there is a demarcated, minimum 44-inch-wide aisle in the back area/stockroom which is allowed for Egress through intervening spaces per IBC 1016.2 Exception 2 Means of egress are not prohibited through stockrooms.
b. Please update your egress plan to show the path of travel that lead directly from the retail area to the exit without obstructions at the stockroom area.
c. Do add the same information at the point of exit as you already have on the other exits.
d. Please do add at each exit the total distance traveled from the start point to the exit.
2. BUILDING CODE SUMMARY
a. Please add the ICC A117.1 into your list of applicable codes.
i. Specifically ICC A117.1 - 2017 Accessible and Usable Building and Facilities
2. DRINKING FOUNTAIN
a. Please locate/label the drinking fountain on the Floor Plan.
b. Identify whether it a high and low configuration as required by ICC A117.1.
3. SERVICE SINK
a. Please locate/label the service sink on the Floor Plan.
b. I cannot find it on your plan.
i. It is required per IBC Table 2902.1 Minimum Number of Required Plumbing Fixtures.
4. SHEET A1
a. Where is Note 21 for the storefront.
b. Provide the sheet number and location on the sheet.
c. Please provide the Solar Heat Gain Coefficient (SHGC) and the U value.
5. Please resubmit.
03/02/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00154
ADDRESS/PARCEL: 615 N ALVERNON WY TUCSON, AZ 85711

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.
2. Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Section C403.10.2.1, IECC 2018.
3. Provide information on the sequence of operation for the restroom exhaust fan (i.e., how is the fan controlled?). Reference: Section 403.2.1 (4), IMC 2024.
4. Condensate drains shall be terminated at an approved disposal location (i.e. not onto the roof as stated in Keynote M01 on sheet M-101). Reference: Section 307.2.1.1, IMC 2024, as amended by the City of Tucson.
5. For the City of Tucson (Climate Zone 2B), the summer design conditions are a dry bulb temperature of 105 °F and a wet bulb temperature of 66 °F. Please update the HVAC Load Schedule Table accordingly. Reference: Table R302.1, IECC 2018.
5. Please provide the cooling capacity of the existing HVAC units to justify the proposed addition of the new RTU. Include all relevant information in the Package Rooftop Unit Schedule, including the sensible cooling capacity of the new RTU. Reference: Section 107.2.1, IBC 2024.
03/02/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00154
ADDRESS/PARCEL: 615 N ALVERNON WY TUCSON, AZ 85711

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

Plumbing
1. Detail D/A1.2 (mop sink and utility cabinet elevation) does not appear to be specified on the floor plan. Please specify where it’s located on the floor plan. Reference: Section 107.2.1, IBC 2024.
2. Specify how the drinking fountain connects to nearest CW line and drain line. Is it connected to the exiting lines from the previous water cooler? Reference: Section 107.2.1, IBC 2024
3. Revise the Building Code Summary to include the adopted 2024 Fuel Gas Code and the 2018 Energy Conservation Code. Reference: Section 107.2.1, IBC 2024.
03/03/2026 Fire New Construction Standard REVIEW COMPLETED
02/06/2026 PDSD Application Completeness Express REVIEW COMPLETED