Permit Number: TC-COM-0226-00150
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0226-00150
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2026 Commercial Building Standard APPROVED
04/21/2026 Commercial Electrical Standard APPROVED
04/30/2026 Commercial Plumbing Standard APPROVED
04/21/2026 Outdoor Lighting Standard APPROVED
05/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/30/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide the Minimum Annual Walk-in Energy Factor (AWEF, Btu/Wh) for the two units. [Initial comment: Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Tables C403.12.2.1(2) and Table C403.12.2.1(3), IECC 2024. Reference: Section C403.12.2, IECC 2024.]
2. The roof is not an approved location for termination of the condensate drain. [Initial comment: Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/13/2026 Addressing Validation REVIEW COMPLETED Unit updated to 101
04/13/2026 PDSD Application Completeness Express REVIEW COMPLETED