Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0226-00150
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2026 | Commercial Building Standard | APPROVED | |||
| 04/21/2026 | Commercial Electrical Standard | APPROVED | |||
| 04/30/2026 | Commercial Plumbing Standard | APPROVED | |||
| 04/21/2026 | Outdoor Lighting Standard | APPROVED | |||
| 05/04/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/30/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide the Minimum Annual Walk-in Energy Factor (AWEF, Btu/Wh) for the two units. [Initial comment: Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Tables C403.12.2.1(2) and Table C403.12.2.1(3), IECC 2024. Reference: Section C403.12.2, IECC 2024.] 2. The roof is not an approved location for termination of the condensate drain. [Initial comment: Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 04/13/2026 | Addressing Validation | REVIEW COMPLETED | Unit updated to 101 | ||
| 04/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |