Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0225-00404
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/21/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. The submitted drawings do not show a hot water recirculation system. [Initial comment: The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.]
2. The submitted drawings do not show a relocated drinking fountain. [Initial comment: Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.]
3. The submitted drawings do not show the installation of a service sink. [Initial comment: Verify that a service sink, required by Table 2902.1 and Section 2902.2, IBC 2018, for business occupancy, is present in the combined suite.]
04/30/2025 PDSD Application Completeness Express REVIEW COMPLETED