Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0225-00404
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/21/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. The submitted drawings do not show a hot water recirculation system. [Initial comment: The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.] 2. The submitted drawings do not show a relocated drinking fountain. [Initial comment: Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.] 3. The submitted drawings do not show the installation of a service sink. [Initial comment: Verify that a service sink, required by Table 2902.1 and Section 2902.2, IBC 2018, for business occupancy, is present in the combined suite.] |
||
| 04/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |