Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00404
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2025 Commercial Building Standard APPROVED
03/13/2025 Commercial Electrical Standard APPROVED
03/24/2025 Commercial Mechanical Standard APPROVED
03/20/2025 Site Zoning Standard APPROVED
03/28/2025 Site Engineering Standard NOT REQUIRED
03/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/24/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.
2. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.
3. Verify that a service sink, required by Table 2902.1 and Section 2902.2, IBC 2018, for business occupancy, is present in the combined suite.
03/04/2025 Fire New Construction Standard REVIEW COMPLETED
03/03/2025 PDSD Application Completeness Express REVIEW COMPLETED