Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0225-00404
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2025 | Commercial Building Standard | APPROVED | |||
| 03/13/2025 | Commercial Electrical Standard | APPROVED | |||
| 03/24/2025 | Commercial Mechanical Standard | APPROVED | |||
| 03/20/2025 | Site Zoning Standard | APPROVED | |||
| 03/28/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 03/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/24/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018. 2. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018. 3. Verify that a service sink, required by Table 2902.1 and Section 2902.2, IBC 2018, for business occupancy, is present in the combined suite. |
||
| 03/04/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 03/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |