Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0225-00397
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
03/10/2025 | Commercial Electrical Fast | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0225-00397 (4383 E PIMA ST TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. 2. Provide an electrical plan showing any/all electrical work required for the lighting upgrade. 3. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. 4. Provide an updated panel schedule, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4. 5. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
03/10/2025 | Outdoor Lighting Fast | REQUIRES RESUBMIT | Outdoor lighting Review TC-COM-0225-00397 (4383 E PIMA ST TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Outdoor Lighting Review: 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. 2. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan 3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 4. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 5. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. 6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 7. Specify any exceptions used. 8. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
03/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |