Permit Number: TC-COM-0225-00396
Parcel: 13205006A

Address:
3225 E 36TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0225-00396
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/05/2025 Commercial Electrical Fast REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00396 (3225 E 36TH ST TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

1. Demonstrate compliance with NEC 230.2 (Number of Services). Must have written consent from the Building Official through appeal.
2. Show the location of the two subpanels on the Electrical Site-Plan with clear working space compliance, 2017 NEC 110.26(A).
3. Clarify if these two subpanels are new with new loads and provide panel schedules showing the circuits that are being modified and added.
a. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.
b. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/27/2025 PDSD Application Completeness Express REVIEW COMPLETED