Permit Number: TC-COM-0225-00389
Parcel: 11703180A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.3

Permit Number - TC-COM-0225-00389
Review Name: COMMERCIAL REVIEW - FULL REVISION v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/08/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0225-00389
ADDRESS/PARCEL: 325 W 2ND ST Unit:BLDG 1 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please revise the outside air calculations on Sheet M301.1 to classify the area served by Unit HP-2 as a kitchen only. The plans currently identify HP-2 as serving a kitchen, retail, and office, but the return air is located in the grab-and-go area. In accordance with footnote (b) of Table 403.3.1.1, air from kitchen spaces shall not be recirculated to other occupancies. Therefore, the entire area served by HP-2 shall be treated as a kitchen, and the outside air calculations shall be revised accordingly. Reference: Table 403.3.1.1, Footnote (b), 2018 IMC.
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED