Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.3
Permit Number - TC-COM-0225-00389
Review Name: COMMERCIAL REVIEW - FULL REVISION v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/08/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0225-00389 ADDRESS/PARCEL: 325 W 2ND ST Unit:BLDG 1 TUCSON, AZ 85705 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Please revise the outside air calculations on Sheet M301.1 to classify the area served by Unit HP-2 as a kitchen only. The plans currently identify HP-2 as serving a kitchen, retail, and office, but the return air is located in the grab-and-go area. In accordance with footnote (b) of Table 403.3.1.1, air from kitchen spaces shall not be recirculated to other occupancies. Therefore, the entire area served by HP-2 shall be treated as a kitchen, and the outside air calculations shall be revised accordingly. Reference: Table 403.3.1.1, Footnote (b), 2018 IMC. |
||
| 06/16/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |