Permit Number: TC-COM-0225-00386
Parcel: 10707003Q

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00386
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2025 Water - PDSD Standard APPROVED
03/08/2025 Outdoor Lighting Standard NOT REQUIRED There is no external lighting involved with this interior tenant improvement.
03/28/2025 Site Engineering Standard NOT REQUIRED
03/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/08/2025 Commercial Building Standard REQUIRES RESUBMIT March 6, 2025
1st Review

CMA LLC
Attn: Chuck Meyer
11598 W. Rock Village Street
Tucson, Arizona 85658

Re: EARTHS HEALING INFUSION KITCHEN
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0225-00386
Stantec Project Number: 185215066
Stantec File Number: TUC-25-028

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 III-B 665 4 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: None.

GENERAL COMMENTS

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2] {Please note: If a Type I Hood is required that the shop drawings are provided or indicated as deferred and the hood suppression system is indicated as a separate submittal as well.}

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2]

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604]

2. Please provide isometric plans for the proposed sewer and supply lines. [Ref. IPC 2018 Sec. 106.3.1]

Sheet P121

1. The proposed 3-compartment sink must be connected to the grease interceptor waste line. [Ref. IPC 2018 Sec. 1003.3 as amended by City of Tucson]]

2. Please provide updated grease interceptor sizing calculations to ensure the existing interceptor will accept the additional fixture. [Ref IPC 2018 Sec. 1003.3 as amended by City of Tucson]

3. The sewer plan does not indicate a connection to fixture S-2. Please indicate a drain line from fixture S-2.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/08/2025 Commercial Electrical Standard REQUIRES RESUBMIT March 6, 2025
1st Review

CMA LLC
Attn: Chuck Meyer
11598 W. Rock Village Street
Tucson, Arizona 85658

Re: EARTHS HEALING INFUSION KITCHEN
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0225-00386
Stantec Project Number: 185215066
Stantec File Number: TUC-25-028

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 III-B 665 4 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: None.

GENERAL COMMENTS

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2] {Please note: If a Type I Hood is required that the shop drawings are provided or indicated as deferred and the hood suppression system is indicated as a separate submittal as well.}

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2]

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604]

2. Please provide isometric plans for the proposed sewer and supply lines. [Ref. IPC 2018 Sec. 106.3.1]

Sheet P121

1. The proposed 3-compartment sink must be connected to the grease interceptor waste line. [Ref. IPC 2018 Sec. 1003.3 as amended by City of Tucson]]

2. Please provide updated grease interceptor sizing calculations to ensure the existing interceptor will accept the additional fixture. [Ref IPC 2018 Sec. 1003.3 as amended by City of Tucson]

3. The sewer plan does not indicate a connection to fixture S-2. Please indicate a drain line from fixture S-2.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/08/2025 Commercial Mechanical Standard REQUIRES RESUBMIT March 6, 2025
1st Review

CMA LLC
Attn: Chuck Meyer
11598 W. Rock Village Street
Tucson, Arizona 85658

Re: EARTHS HEALING INFUSION KITCHEN
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0225-00386
Stantec Project Number: 185215066
Stantec File Number: TUC-25-028

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 III-B 665 4 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: None.

GENERAL COMMENTS

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2] {Please note: If a Type I Hood is required that the shop drawings are provided or indicated as deferred and the hood suppression system is indicated as a separate submittal as well.}

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2]

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604]

2. Please provide isometric plans for the proposed sewer and supply lines. [Ref. IPC 2018 Sec. 106.3.1]

Sheet P121

1. The proposed 3-compartment sink must be connected to the grease interceptor waste line. [Ref. IPC 2018 Sec. 1003.3 as amended by City of Tucson]]

2. Please provide updated grease interceptor sizing calculations to ensure the existing interceptor will accept the additional fixture. [Ref IPC 2018 Sec. 1003.3 as amended by City of Tucson]

3. The sewer plan does not indicate a connection to fixture S-2. Please indicate a drain line from fixture S-2.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/18/2025 Commercial Mechanical Standard REQUIRES RESUBMIT The current mechanical design does not provide any form of the required odor mitigation. Reference: City of Tucson Ordinance 11828 Sec. 4.9.9.E.1.I.
03/08/2025 Commercial Plumbing Standard REQUIRES RESUBMIT March 6, 2025
1st Review

CMA LLC
Attn: Chuck Meyer
11598 W. Rock Village Street
Tucson, Arizona 85658

Re: EARTHS HEALING INFUSION KITCHEN
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0225-00386
Stantec Project Number: 185215066
Stantec File Number: TUC-25-028

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 III-B 665 4 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: None.

GENERAL COMMENTS

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2] {Please note: If a Type I Hood is required that the shop drawings are provided or indicated as deferred and the hood suppression system is indicated as a separate submittal as well.}

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. The plans indicate that the tenant improvement is proposing a new Type II Hood. The appliances that the new hood is to serve appear to be induction ranges. The equipment schedule on Sheet FS1 describes this equipment only as “induction”. Induction ranges qualify as medium-duty cooking appliances which require Type I Hoods. Please clarify on the plans what type of “induction” equipment is being served and revise the plans accordingly, if required. [Ref. IMC 2018 Sec. 202 & 507.2]

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604]

2. Please provide isometric plans for the proposed sewer and supply lines. [Ref. IPC 2018 Sec. 106.3.1]

Sheet P121

1. The proposed 3-compartment sink must be connected to the grease interceptor waste line. [Ref. IPC 2018 Sec. 1003.3 as amended by City of Tucson]]

2. Please provide updated grease interceptor sizing calculations to ensure the existing interceptor will accept the additional fixture. [Ref IPC 2018 Sec. 1003.3 as amended by City of Tucson]

3. The sewer plan does not indicate a connection to fixture S-2. Please indicate a drain line from fixture S-2.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/20/2025 Site Zoning Standard REQUIRES RESUBMIT 1. Please demonstrate compliance with applicable use specific standard, UDC 4.9.9.E.1.I - Odor mitigation devices and techniques shall be incorporated in all marijuana facilities to ensure that odors are mitigated. As such, this may be done through an exhaust air filtration system with odor control that prevents internal odors from being emitted externally or through any other best practices deemed adequate for odor mitigation as determined by the Zoning Administrator.

An odor mitigation plan shall be submitted demonstrating compliance with odor control requirement.

Loran Shamis
Loran.Shamis@tucsonaz.gov
03/06/2025 Fire New Construction Standard REVIEW COMPLETED The addition of a hood fire suppression will required a separate permit per the 2024 IFC.