Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0225-00386
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/16/2025 | Commercial Building Standard | REQUIRES RESUBMIT | April 16, 2025 2nd Review CMA LLC Attn: Chuck Meyer 11598 W. Rock Village Street Tucson, Arizona 85658 Re: EARTHS HEALING INFUSION KITCHEN TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0225-00386 Stantec Project Number: 185215066 Stantec File Number: TUC-25-028 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms F-1 III-B 665 4 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system. Deferred Submittals: None. Special Inspections: None. GENERAL COMMENTS 1. Addressed. 2. New Comment: The 2nd submittal did not include the structural calculations. All documents must be reuploaded with each new submittal. Please ensure that all documents are reuploaded with the next submittal. This should include the following: Construction documents, structural calculations, response letter, supplemental email. ARCHITECTURAL COMMENTS General 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. Addressed. PLUMBING COMMENTS General 1. Previous Comment: Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604] Still Required: The water pressure calculations were submitted with the response letter. These calculations must be included in the plumbing set of the construction drawings. 2. Addressed. Sheet P121 1. Addressed. 2. Addressed. 3. Addressed. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 04/16/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | April 16, 2025 2nd Review CMA LLC Attn: Chuck Meyer 11598 W. Rock Village Street Tucson, Arizona 85658 Re: EARTHS HEALING INFUSION KITCHEN TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0225-00386 Stantec Project Number: 185215066 Stantec File Number: TUC-25-028 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms F-1 III-B 665 4 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system. Deferred Submittals: None. Special Inspections: None. GENERAL COMMENTS 1. Addressed. 2. New Comment: The 2nd submittal did not include the structural calculations. All documents must be reuploaded with each new submittal. Please ensure that all documents are reuploaded with the next submittal. This should include the following: Construction documents, structural calculations, response letter, supplemental email. ARCHITECTURAL COMMENTS General 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. Addressed. PLUMBING COMMENTS General 1. Previous Comment: Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604] Still Required: The water pressure calculations were submitted with the response letter. These calculations must be included in the plumbing set of the construction drawings. 2. Addressed. Sheet P121 1. Addressed. 2. Addressed. 3. Addressed. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 04/16/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | April 16, 2025 2nd Review CMA LLC Attn: Chuck Meyer 11598 W. Rock Village Street Tucson, Arizona 85658 Re: EARTHS HEALING INFUSION KITCHEN TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0225-00386 Stantec Project Number: 185215066 Stantec File Number: TUC-25-028 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms F-1 III-B 665 4 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system. Deferred Submittals: None. Special Inspections: None. GENERAL COMMENTS 1. Addressed. 2. New Comment: The 2nd submittal did not include the structural calculations. All documents must be reuploaded with each new submittal. Please ensure that all documents are reuploaded with the next submittal. This should include the following: Construction documents, structural calculations, response letter, supplemental email. ARCHITECTURAL COMMENTS General 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. Addressed. PLUMBING COMMENTS General 1. Previous Comment: Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604] Still Required: The water pressure calculations were submitted with the response letter. These calculations must be included in the plumbing set of the construction drawings. 2. Addressed. Sheet P121 1. Addressed. 2. Addressed. 3. Addressed. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 04/30/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ODOR MITIGATION REQUESTED BY ZONING The manufacturer’s literature for the RGF QRP-9 Guardian Photohydroionization cell unit addresses its use in HVAC systems but not exhaust ducts from Type II hoods. Provide installation instructions from the manufacturer for this application along with supporting data attesting to the effectiveness of the unit to mitigate odors in this application. Show how the exhaust for existing hood is being addressed. [Initial comment: The current mechanical design does not provide any form of the required odor mitigation. Reference: City of Tucson Ordinance 11828 Sec. 4.9.9.E.1.I.] |
||
| 04/16/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | April 16, 2025 2nd Review CMA LLC Attn: Chuck Meyer 11598 W. Rock Village Street Tucson, Arizona 85658 Re: EARTHS HEALING INFUSION KITCHEN TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0225-00386 Stantec Project Number: 185215066 Stantec File Number: TUC-25-028 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms F-1 III-B 665 4 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system. Deferred Submittals: None. Special Inspections: None. GENERAL COMMENTS 1. Addressed. 2. New Comment: The 2nd submittal did not include the structural calculations. All documents must be reuploaded with each new submittal. Please ensure that all documents are reuploaded with the next submittal. This should include the following: Construction documents, structural calculations, response letter, supplemental email. ARCHITECTURAL COMMENTS General 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. Addressed. PLUMBING COMMENTS General 1. Previous Comment: Please provide updated water pressure calculations with the added fixtures. [Ref. IPC 2018 Sec. 604] Still Required: The water pressure calculations were submitted with the response letter. These calculations must be included in the plumbing set of the construction drawings. 2. Addressed. Sheet P121 1. Addressed. 2. Addressed. 3. Addressed. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 04/30/2025 | Site Zoning Standard | REQUIRES RESUBMIT | 1. COMMENT: Please address City of Tucson Commercial Mechanical comment regarding the Odor Mitigation systems. Demonstrate compliance with applicable use specific standard, UDC 4.9.9.E.1.I - Odor mitigation devices and techniques shall be incorporated in all marijuana facilities to ensure that odors are mitigated. As such, this may be done through an exhaust air filtration system with odor control that prevents internal odors from being emitted externally or through any other best practices deemed adequate for odor mitigation as determined by the Zoning Administrator. An odor mitigation plan shall be submitted demonstrating compliance with odor control requirement. Loran Shamis Loran.Shamis@tucsonaz.gov |
||
| 04/09/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |