Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0225-00385
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2025 | Commercial Building | APPROVED | |||
| 03/14/2025 | Water - PDSD | APPROVED | |||
| 03/07/2025 | Outdoor Lighting | NOT REQUIRED | No changes to the outdoor lighting. | ||
| 03/27/2025 | Site Engineering | NOT REQUIRED | |||
| 03/27/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/07/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0225-00385 (9484 E 22ND ST Unit:UNIT 120 TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. A signature and date are required as part of the Registrant Seal (Electrical). Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed. >>> Seal is missing date signed. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/14/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted during the hours of operation. Reference: Section 403.2.1 (4), IMC 2018. | ||
| 03/14/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide metering faucets for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
||
| 03/14/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0225-00385 9484 E 22ND ST Unit: 120. - C-1 Medical Services: Outpatient (1st Review) TRANSMITTAL DATE: March 14, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-1 zone (UDC 4.7.20). Medical Services: Outpatient is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.O.2 and 4.9.13.O. 1. This site was approved under Development Package DP12-0188 with food service of 4,311 SF of building with 706 SF of patio for a total of 5,017 SF /100 requiring 50 parking space and furniture, carpet or appliance store of 3,853 SF / 400 requiring 10 parking spaces with a total of 61 spaces provided. The proposed medical service, outpatient, parking requirement is 1 space per 200 SF of Gross Floor Area. As the proposed medical service, outpatient, TI is proposed in a portion of the space originally approved as furniture, carpet or appliance store, provide a vehicle parking space calculation that clearly shows the breakdown of current and proposed uses and their required vehicle parking requirement. If you are able to meet the required number of vehicle parking spaces some type of variance or exception will need to be completed. Review UDC Article 7.4 for applicable requirements and exceptions. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 03/04/2025 | Fire New Construction | REVIEW COMPLETED | Fire Sprinklers deferred submittal s shall comply with the 2024 IFC. | ||
| 02/28/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |