Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0225-00385
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2025 Site Zoning APPROVED
07/15/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2025 Commercial Mechanical REQUIRES RESUBMIT The comment response letter stated that a “tag /label” was to be at the restroom door calling for the fan to be turned on during occupied hours and turned off during unoccupied hours. This note was not added to the plans; the fan schedule still calls for the fan to be controlled by an occupancy sensor. Why not just call for a time clock to control the fan? [Second comment: Provide testing data to show that the backdraft damper will open at 0.05” WG and the 4” exhaust duct will pass 75 CFM without the aid of an exhaust fan. Reference: Section 107.2.1, IBC 2018.] [Initial comment: Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted during the hours of operation. Reference: Section 403.2.1 (4), IMC 2018.]