Permit Number: TC-COM-0225-00381
Parcel: 140290630

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0225-00381
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/17/2025 Commercial Plumbing Fast REQUIRES RESUBMIT 1. Seal drawing sheet P1.0. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a detail showing the connection of the effluent of the sump pump to the sanitary drain system as described in Section 712.3.5, IPC 2018. Reference: Section 712.1, IPC 2018.
3. Revise the size of the building sub-drain per Table 710.1(1), IPC 2018. Reference: Section 709.3, IPC 2018.
4. Clarify keynote #1 on sheet P1.0 regarding the connection of the new sub-drain to the existing drainage system. Reference: Section 107.2.1, IBC 2018.
03/10/2025 PDSD Application Completeness Express REVIEW COMPLETED