Permit Number: TC-COM-0225-00358
Parcel: 128030110

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0225-00358
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2025 Commercial Electrical Fast REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0225-00358 (5700 E BROADWAY BL TUCSON, AZ 85711)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), International Energy Conservation Code (IECC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).


Outdoor Lighting Review:

1. The ‘Max Lumens Allowed’ is incorrect for the Parcel Area given. Given option 2, from Table 401.1, the Max Lumens Allowed should be 130,500.
2. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.

3. Per 106.2.1, this site uses 79.7% of the allowable Lumens from Table 401.1. Provide a Special Inspection Certificate, with parts A and B completed and sealed. Indicate on the plans if a special inspection is required per sec. 104.2.2, and 106.2.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/07/2025 Outdoor Lighting Fast REQUIRES RESUBMIT Demonstrate compliance with NEC 230.2 (Number of Services). Must have written consent from the Building Official through appeal.
05/07/2025 PDSD Application Completeness Express REVIEW COMPLETED
05/08/2025 Signs Fast REVIEW COMPLETED Not applicable to sign review