Permit Number: TC-COM-0225-00356
Parcel: 12105030A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0225-00356
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2025 Commercial Building Standard APPROVED
04/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/22/2025 Commercial Plumbing Standard REQUIRES RESUBMIT The location of the emergency eyewash within a lockable, single-user restroom does not comply with the requirements of ANSI/ISEA Z358.1. The emergency shower is to be located within 10-seconds of the hazard and the path of travel must be free of obstructions. Reference: Section 411.1, IPC 2018.
03/28/2025 PDSD Application Completeness Express REVIEW COMPLETED