Permit Number: TC-COM-0225-00352
Parcel: 127040140

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0225-00352
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2026 Commercial Electrical Standard APPROVED
02/12/2026 Commercial Mechanical Standard APPROVED
02/12/2026 Commercial Plumbing Standard APPROVED
02/12/2026 Water - PDSD Standard APPROVED
01/30/2026 Outdoor Lighting Standard NOT REQUIRED no modifications to the outdoor lighting.
02/19/2026 Site Engineering Standard NOT REQUIRED
02/19/2026 Site Zoning Standard NOT REQUIRED
02/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/18/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please recalculate the occupant load using Net Floor area as required by IBC table 1004.5 as the total occupant load appears to exceed 49.
2. Please provide the following information on the floor plan.
A. All spaces are labeled with a name or further description as needed to adequately convey the intended purpose (use) or the multiple uses of the space. IBC 302.1 For example Flex Space is not defined in the IBC and What is the Accessory Occupancy? This should likely be a part of the B occupancy,
B. All spaces are labeled with their occupancy classification or classifications. IBC 302.1
3. Please provide the following information means of egress information on the plans.
A. The total number of occupants for the story or floor is shown. IBC 107.2.3
B. The number of occupants is shown for every room and space. IBC 107.2.3
C. The occupant load factor and area are shown for every room and space. IBC 1004.5
D. The occupant load factor used reflects the use/function of the space. IBC 1004.5
E. The area of aisles and aisle accessways are included in net area. IBC 1004.5
F. The number of occupants being served by each egress door and stairway is shown. IBC 107.2.3
G. Doors serving a space with ≥ 50 people swing in the direction of egress travel. IBC 1010.1.2.1
H. Doors serving a space with ≥ 50 people in A or occupancies have panic hardware. IBC 1010.1.10




Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/20/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581