Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0225-00334
Parcel: 10713107D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0225-00334
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2026 Commercial Structural Standard APPROVED
03/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/24/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00334 (2650 N ORACLE RD Unit:UNIT 421 TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Panelboards shall not be located in the bathroom NEC 240.24(E). Show New Sub-panel ‘A’ in code compliant location.
2. Show the door swing of the sub-panel’s door. Clear working space must be maintained from the floor and for the dimensions in 2017 NEC 110.26(A).
02/24/2026 PDSD Application Completeness Express REVIEW COMPLETED