Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0225-00334
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2026 | Commercial Structural Standard | APPROVED | |||
| 03/13/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/24/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0225-00334 (2650 N ORACLE RD Unit:UNIT 421 TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Panelboards shall not be located in the bathroom NEC 240.24(E). Show New Sub-panel ‘A’ in code compliant location. 2. Show the door swing of the sub-panel’s door. Clear working space must be maintained from the floor and for the dimensions in 2017 NEC 110.26(A). |
||
| 02/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |