Permit Number: TC-COM-0225-00321
Parcel: 111075770

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00321
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/14/2025 Addressing Validation REQUIRES RESUBMIT Address location has multiple units. On application it shows as BLDG 1 with no units and plans shows for BLDG 2. Building # and Units will have to be confirmed and assigned to Permit Application and on Plans. Please submit a comment letter and Plans (with BLDG # and unit #'s). Units and Building will need to be confirmed please contact Pima County Addressing at Addressing@pima.gov or 520-724-9512
03/10/2025 Commercial Building Standard REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304




Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/05/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00321 (2510 N WINSTEL BL Unit:BLDG 1 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
2. Provide a complete electrical plan-set showing all proposed electrical work.
3. Should include but not be limited to:
a. Show the location of the panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A).
b. Provide a panel schedule showing the circuits that are being modified and added.
c. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.
d. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/10/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
03/10/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
02/14/2025 PDSD Application Completeness Express REVIEW COMPLETED