Permit Number: TC-COM-0225-00318
Parcel: 11615077K

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00318
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2025 Commercial Plumbing Standard APPROVED
03/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/12/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide the sealed structural calculations used in the design of the new opening and support of the wall above. IBC 107.2.7
2. Please amend the Special Inspections area to list the required special inspections, if required. For example, screw anchors.
Additionally, if required, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf







Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/05/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00318 (1513 W SAINT MARYS RD TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

1. Provide an updated panel schedule for ‘Existing SES Serving This Project (1507), showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
2. Clarify the Service Entrance Load Calculations. Calculations show a total load of 263A, while the meter and panel A rating are 200A. Total square footage used in the calculations does not match the combined square footage of the expanded laundry space shown on sheet C.0. NEC 220.40.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/11/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Revise the condensate drain system to allow for the clearing of blockages without the need to cut the pipe. Reference: Section 307.2.5, IMC 2018.
2. Revise the design for the termination of the clothes dryer exhaust to include a backdraft damper. Reference: Section 504.4, IMC 2018.
03/07/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0225-00318
1513 W SAINT MARYS RD – C-1
Laundromat (1st Review)

TRANSMITTAL DATE: March 7, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Multifamily is a permitted use in this zone (Table 4.8-4). See Use-Specific Standards 4.9.4.T.1 and 4.9.13.O

1. Per Use Specific Standard, UDC 4.9.4.T.1 Article Laundry facilities shall not exceed 3,000 square feet of floor area. As the proposed laundromat exceeds the allowed square footage a Board of Adjustment for Variance will need to be approved prior to approval of this permit. Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. Contact for the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/20/2025 Fire New Construction Standard REVIEW COMPLETED Any modifications to the fire alarm or fire sprinklers requires a separate permit. The most current adopted fire code is the 2024 IFC with local amendments.
02/18/2025 PDSD Application Completeness Express REVIEW COMPLETED
03/17/2025 Site Engineering Standard REVIEW COMPLETED