Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0225-00313
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2025 | Commercial Building | APPROVED | |||
| 03/04/2025 | Commercial Mechanical | APPROVED | |||
| 03/04/2025 | Commercial Plumbing | APPROVED | |||
| 03/04/2025 | Water - PDSD | APPROVED | |||
| 02/22/2025 | Outdoor Lighting | NOT REQUIRED | No changes to the outdoor lighting. | ||
| 03/10/2025 | Site Engineering | NOT REQUIRED | |||
| 03/03/2025 | Site Zoning | NOT REQUIRED | Charter School Exemption see T13SA00040 letter dated 2/20/2013 | ||
| 03/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/21/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0225-00313 (510 S HIGHLAND AV TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide a complete electrical plan showing all the new work. The provided panel schedule shows multiple new circuits that cannot be located on the provided Ceiling & Electrical Plan. 2. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4. 3. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4. 4. Show GFCI protected receptacle in the new bathroom per NEC requirements. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/19/2025 | Fire New Construction | REVIEW COMPLETED | The fire alarm submittal shall comply with the 2024 IFC and NFPA72, 2022 Edition. | ||
| 02/18/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |