Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0225-00288
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 3/11/2025 11:45:59 AM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 3/11/2025 11:45:42 AM |
||
| 03/03/2025 | Commercial Electrical Standard | APPROVED | |||
| 03/06/2025 | Commercial Plumbing Standard | APPROVED | |||
| 03/04/2025 | Site Zoning Standard | APPROVED | |||
| 03/12/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 03/12/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/06/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Recirculation of air from restrooms is not allowed; the exhaust flowrate shall be at least equal to the supply air flowrate. Revise the sequence of operation for the exhaust fans so that all of the air supplied to the restrooms will be exhausted during the hours of operation. Reference: Footnote g, Table 403.1.1, IMC 2018. | ||
| 02/20/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 02/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |