Permit Number: TC-COM-0225-00288
Parcel: 120072150

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00288
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/11/2025 11:45:59 AM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/11/2025 11:45:42 AM
03/03/2025 Commercial Electrical Standard APPROVED
03/06/2025 Commercial Plumbing Standard APPROVED
03/04/2025 Site Zoning Standard APPROVED
03/12/2025 Site Engineering Standard NOT REQUIRED
03/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Recirculation of air from restrooms is not allowed; the exhaust flowrate shall be at least equal to the supply air flowrate. Revise the sequence of operation for the exhaust fans so that all of the air supplied to the restrooms will be exhausted during the hours of operation. Reference: Footnote g, Table 403.1.1, IMC 2018.
02/20/2025 Fire New Construction Standard REVIEW COMPLETED
02/12/2025 PDSD Application Completeness Express REVIEW COMPLETED