Permit Number: TC-COM-0225-00285
Parcel: Unknown

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0225-00285
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2025 Commercial Electrical Standard APPROVED
06/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/30/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide mechanical ventilation for the apartment. Reference: Sections R403.6 and R503.1.2, IECC 2018. [Initial comment: Provide calculations demonstrating adequate ventilation using Section 403.3.2.1, IMC 2018. Note that the minimum continuous and intermittent exhaust airflow rates for kitchens and bathrooms required by Section 403.3.2.3, IMC 2018 are still required.
2. The mechanical plan shows the kitchen exhaust hood terminating into the adjacent unit. Reference: Section 107.2.1, IBC. [Initial comment: Clarify the operation of the specified kitchen hood. Will the unit be set up for exhaust or recirculation? Reference: Sections 403.3.2.3 and 505.3, exception 1, IMC 2018.
06/30/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Show how the T&P relief will be, “plumb[ed] to daylight.” Show the route & termination of the pan drain. Reference: Sections 504.6 and 504.7, IPC 2018.
06/06/2025 PDSD Application Completeness Express REVIEW COMPLETED