Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0225-00280
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2025 Commercial Electrical Standard APPROVED
09/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/24/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Show that the new fenestration components (e.g. windows) comply with the requirements of Table R402.1.2, IECC 2018. Reference: Sections R402.1.2 and R501.5, International Energy Conservation Code 2018. In Climate Zone 2 (Per Table R402.1.2) the fenestration U-factor should be 0.40.
09/24/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Please show an accurate representation of the water heater in the water heater diagram. Clarify how the specified water heater will be able to be maintained or replaced (IPC 501.4 and IPC 502.5)