Permit Number: TC-COM-0225-00266
Parcel: 12809006B

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.3

Permit Number - TC-COM-0225-00266
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/27/2025 Masonry Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0225-00266
PROJECT: Building 4
ADDRESS/PARCEL: 5441 E 22ND ST


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.


COMMENTS:
1. Missing Masonry Inspection Field Reports.
2. Missing Post Installed Anchor Reports.
3. Missing Cold Formed Steel Special Inspection Field Reports.
4. Will need a letter from the registrant as to why the Fabricator’s Inspection is not Applicable as it is called out on Sheet S0.3
5. Going forward when submitting Field Reports, please upload them into categories. EG: Soil reports should be combined and submitted as one document, Concrete Inspections should be combined and submitted as one report.




Please upload your revised plans to TDC-Online with a revision letter outlining what has been revised on the doc set.


If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov
10/27/2025 Other Inspection Reports (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0225-00266
PROJECT: Building 4
ADDRESS/PARCEL: 5441 E 22ND ST


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.


COMMENTS:
1. Missing Masonry Inspection Field Reports.
2. Missing Post Installed Anchor Reports.
3. Missing Cold Formed Steel Special Inspection Field Reports.
4. Will need a letter from the registrant as to why the Fabricator’s Inspection is not Applicable as it is called out on Sheet S0.3
5. Going forward when submitting Field Reports, please upload them into categories. EG: Soil reports should be combined and submitted as one document, Concrete Inspections should be combined and submitted as one report.




Please upload your revised plans to TDC-Online with a revision letter outlining what has been revised on the doc set.


If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov
10/27/2025 Post-Installed Anchor Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0225-00266
PROJECT: Building 4
ADDRESS/PARCEL: 5441 E 22ND ST


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.


COMMENTS:
1. Missing Masonry Inspection Field Reports.
2. Missing Post Installed Anchor Reports.
3. Missing Cold Formed Steel Special Inspection Field Reports.
4. Will need a letter from the registrant as to why the Fabricator’s Inspection is not Applicable as it is called out on Sheet S0.3
5. Going forward when submitting Field Reports, please upload them into categories. EG: Soil reports should be combined and submitted as one document, Concrete Inspections should be combined and submitted as one report.




Please upload your revised plans to TDC-Online with a revision letter outlining what has been revised on the doc set.


If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov
10/27/2025 Concrete Installation Inspection (Deferred Submittal) Express REVIEW COMPLETED
10/22/2025 PDSD Application Completeness Express REVIEW COMPLETED