Permit Number: TC-COM-0225-00252
Parcel: 12801005H

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0225-00252
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT Provide an air balancing report to verify that the HVAC systems are capable of supplying and exhausting at least the minimum air flow rates called for in the design drawings. The balancing shall be performed by a qualified balancing contractor in accordance with the procedural standards of either the National Environmental Balancing Bureau (NEBB) or the Associated Air Balance Council (AABC). Reference: Section 403.3.1.5, IMC 2018 as amended by the City of Tucson.
09/17/2025 PDSD Application Completeness Express REVIEW COMPLETED