Permit Number: TC-COM-0225-00247
Parcel: 14118001K

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0225-00247
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2025 Commercial Mechanical Fast REQUIRES RESUBMIT Provide the heating/cooling load calculations for AC-2. [Initial comment: Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.]
02/21/2025 PDSD Application Completeness Express REVIEW COMPLETED