Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0225-00247
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/27/2025 | Commercial Mechanical Fast | REQUIRES RESUBMIT | Provide the heating/cooling load calculations for AC-2. [Initial comment: Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.] | ||
| 02/21/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |