Permit Number: TC-COM-0225-00246
Parcel: 13727652A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0225-00246
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/13/2025 Commercial Mechanical Fast REQUIRES RESUBMIT Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2018). While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
02/10/2025 PDSD Application Completeness Express REVIEW COMPLETED