Permit Number: TC-COM-0225-00242
Parcel: 110113670

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00242
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2025 Commercial Mechanical Standard APPROVED
03/03/2025 Water - PDSD Standard APPROVED
03/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/19/2025 Commercial Building Standard REQUIRES RESUBMIT For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM)
1. Sheet a3.2 Provide thermal envelope compliance certificate that identifies new glass doors at new openings. Incomplete 2018 IECC R503.1.1 (BM)
2. Sheet a4.0 RCP key note 412 identifies (n)GWB ceiling, paint. Plan appears to be grid ACT at dinning / kitchen area identified by key note 401. Clarify 2018 IBC 107.2.1 (BM)
3. Sheet S1.2 Provide completed special inspection form for required items identified in plans. Incomplete 2018 IBC 1705 (BM)
02/19/2025 Commercial Electrical Standard REQUIRES RESUBMIT 1. Sheet e1.1 Provide for review, existing and new exterior EM egress lights and exit signs for existing and new exits from building and patio area along with EM lighting at new patio. Not complete. 2018 IBC section 1008 & 1013 (BM)
2. e2.2 Key note 7, clarify roof top maintenance receptacles meet spacing per 2017 NEC 210.63 (BM), only two are identified on roof
02/19/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet p3.0 Sheet p1.2 identifies new gas supply from meter along with an existing system. Provide a complete gas supply schematics to include new system with new and existing appliances and existing system with existing appliances. New riser detail only identifies new kitchen appliances. 2018 IBC 107.2.1 (BM)
2. Sheet p3.1 Water heater detail should identify pan and drain where storage tank is installed in location where water leakage from tank can cause damage. 2018 IPC 504.7 (BM)
3. Sheet p3.1 Provide for review, sediment trap detail for gas supply at each appliance where trap is not incorporated as part of the appliance. 2018 IFGC 408.4 (BM)
4. Sheet p3.1 Provide for review, water heater venting and combustion air riser detail to verify compliance and clearances. Incomplete. 2018 IFGC section 503 & 505 (BM)
03/03/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0225-00242 (4821 E GRANT RD Unit:UNIT 101 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), International Energy Conservation Code (IECC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
3. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.

4. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

5. Specify any exceptions used.

6. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/07/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0225-00242
4821 E GRANT RD UNIT 101

The building permit cannot be approved until the associated development package, TD-DEV-1024-00284, is approved. Per UDC Article 3.3.3.7.a The approved site plan (Development Package) on file with the PDSD is the basis for issuance of building permits.

Chris Arrington
chris.arrington@tucsonaz.gov
03/03/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0225-00242 - TD-DEV-1024-00284
4821 E GRANT RD Unit: 101. - C-2
Food Service (1st Review)

TRANSMITTAL DATE: ‎March 3, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Financial Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.L.3, 4.9.13.E, and 4.9.13.P.

1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-1024-00284 and although it appears that the building plan is in compliance until the DP is approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/10/2025 Fire New Construction Standard REVIEW COMPLETED Any upgrades to the fire alarm, fire sprinklers or hood fire suppression system will require a separate permit. The actual city of Tucson adopted fire code is the 2024 IFC. Fire extinguishers shall comply with the 2024 IFC Section 906
02/08/2025 PDSD Application Completeness Express REVIEW COMPLETED