Permit Number: TC-COM-0225-00236
Parcel: 12509049C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00236
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2025 Commercial Building Standard APPROVED
02/21/2025 Commercial Electrical Standard APPROVED
03/03/2025 Commercial Mechanical Standard APPROVED
03/04/2025 Site Zoning Standard APPROVED
03/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/03/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Clarify General Note #2 on sheet P1. The need for a backwater valve is not determined by the depth of the sewer piping. Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
2. Provide the minimum size for the natural gas branch for the hot plate (#20). Reference: Sections 402.1 and 402.3, IFGC 2018.
3. Verify the size of the existing water meter. Tucson Water records show a 1” water meter, serial number 19221047.
02/10/2025 Fire New Construction Standard REVIEW COMPLETED Fire extinguishers shall be installed accordingly with the 2024 IFC Section 906
02/08/2025 PDSD Application Completeness Express REVIEW COMPLETED