Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0225-00227
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2025 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0225-00227 ADDRESS/PARCEL: (7831 E BROADWAY BL TUCSON, AZ 85710) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. COMMENTS: 1. Provide a complete code analysis. Please do an accurate occupant load calculation. The 101 Closing is an assembly space using 15 net SF for each person as well as 102 Back of House to use 15 net SF per person. Please update your occupant load. 2. Restroom to comply to ICC A117.1 NOTE: no fixture such as the sink cannot encroach into the required clear floor area around the water closet. Please correct this condition.Detail drawings to indicate at every joint using welding callout as to what type of welding is being used (the submitted drawing is not complete when it comes to attachment/fastening used). 3. Sink Counter at the Back of House room and work surface in the Closing room to comply to the required 34 inch high counter surface and 36 inches wide area and the required leg clearance under the work surface per ICC A117.1 Designate an accessible work surface/station in the Office area by showing a wheelchair at that location. 4. At water closet, 60" W x 56" D clearance area on the floor per ANSI A117 Figure 604.3 Ensure no other fixtures are within this area. Lavatory shall be maximum 34 inches above floor to the higher of the rim or counter surface, faucets and soap dispenser shall have a reach depth of 11 inches per ANSI 606.5 The lavatory faucet shall be a metering faucet. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Water supply and drain pipes under lavatories shall be insulated to protect against contact per ANSI 606.6 complying to clearances shown on Figure 606.3 ICC A117.1 5. Install a water fountain or For the business occupancy, water coolers can be substituted for drinking fountains per IBC 2902.1 and IPC 410.1 6. Accessible door opening shall be a minimum clear opening width of 32 inches. The clear opening width of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where a door opening includes two door leaves without a mullion, one leaf shall provide a minimum clear opening width of 32 inches. IBC 1010.1.1. 7. At the front and back door, install sign - This Door To Remain Unlocked When This Space Is Occupied. IBC 1010.1.9.4 THE MEANS OF EGRESS WILL BE ILLUMINATED TO A LEVEL OF NOT LESS THAN ONE FOOT-CANDLE AT THE WALKING SURFACE AT ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS OCCUPIED. IBC 1008.2.1 Locate/label the lighted exit sign, emergency light with back-up power as well as the fire extinguisher. 8. Please resubmit. |
||
| 02/10/2025 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0225-00227 (7831 E BROADWAY BL TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. 2. Provide a complete electrical plan-set showing all proposed electrical work. 3. Should include but not be limited to: a. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. b. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. c. Show the location of the panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A). d. Provide a panel schedule showing the circuits that are being modified and added. e. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4. f. Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable. 4. Additional comments may be required with the submittal of electrical plans. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/24/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Revise the mechanical design as required to provide return air for rooms 101 and 102 to avoid using the egress route as a return air duct. Reference: Section 601.2, IMC 2018. | ||
| 02/24/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Show how hot water is to be supplied to the new sink. Reference: Section 607.1, IPC 2018. 2. Coffee machines connected to the water distribution system require the use of a backflow preventer listed to either ASSE 1022, ASSE 1024, or an air gap. Reference: Section 608.17.1.2, IPC 2018. |
||
| 02/24/2025 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Ramiro Olivarez Zoning Review Section PROJECT: TC-COM-0225-00227 7831 E BROADWAY BL – C-1 Zoning TI/Certificate of Occupancy Financial Service (1st Review) TRANSMITTAL DATE: 02/24/2025 This site is located in the C-1 zone (UDC 4.7.20). COMMENTS: Please resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Comment: The Use of this space applied for is recognized and reviewed as a Financial Service: Non-chartered Institution. Financial Service: Non-chartered Institution is Not an allowed Use in the C-1 Zone. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-2103 If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov |
||
| 02/07/2025 | Fire New Construction | REVIEW COMPLETED | The fire sprinklers system fire flow and tamper signals shall be monitored by a fire alarm system. | ||