Permit Number: TC-COM-0225-00215
Parcel: 12105012G

Address:
5502 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00215
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/18/2025 5:31:38 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 2/7/2025 1:30:09 PM
02/19/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/13/2025 5:33:11 PM
02/19/2025 Outdoor Lighting Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/13/2025 5:33:11 PM
03/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/19/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/17/2025 9:48:58 AM
1. General - Provide Heat Load calculations - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
02/19/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/18/2025 11:12:52 PM
First Plumbing Review:
1). Plan Page A1.3: Missing Lavatory Fixture spacing Measurements. Add Lavatory Fixture spacing Measurements.. -2018
IPC 405.3.1
2). Plan Page P1.1.1: Indirect waste piping that exceeds distances listed in -2018 IPC 802.3 shall be trapped. Update detail
#2 to comply with -2018 IPC 802.3
3). Plan page P1.3 : Water piping to H201 (oven) needs backflow protection. Add Backflow protection device to H201 oven
water connection -2018 IPC 608.3
4). Plan Page P1.2: Water riser missing the H201 oven water line. Add the H201 oven water line to the water riser. -2018 IPC
106.3.1
5). Plan Page P1.2 grease interceptor load table: The Floor sinks & floor drains can't have a DFU load of zero. Update the
Grease interceptor load table with DFU amounts derived from -2018 IPC section 709 thru 709.4.1
03/05/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0225-00215
5502 E GRANT RD

Site Engineering approval for this permit cannot be granted until the associated development package (DP) -- TD-DEV-0924-00266 -- is issued. Although the DP is approved, outstanding pre-issuance conditions remain.

Chris Arrington
chris.arrington@tucsonaz.gov
03/03/2025 Site Zoning Standard REQUIRES RESUBMIT Although the plans appear to match, final Site Zoning approval for this permit cannot be granted until the associated development package (DP) -- TD-DEV-0924-00266 -- is issued. Although the DP has received all approval, outstanding pre-issuance conditions remain.

Please reach out in case of any questions to fernando.garcia2@tucsonaz.gov.
02/26/2025 Water - PDSD Standard REQUIRES RESUBMIT Show the location and size of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
02/14/2025 Fire New Construction Standard REVIEW COMPLETED The CO2 system requires a separate operational permit per the 2024 IFC and local amendments.
Install fire extinguishers as required per section 906, 2024 IFC.
02/05/2025 PDSD Application Completeness Express REVIEW COMPLETED