Permit Number: TC-COM-0225-00215
Parcel: 12105012G

Address:
5502 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0225-00215
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/25/2025 9:13:55 AM
04/10/2025 Water - PDSD Standard APPROVED
04/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/25/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 3/23/2025 6:10:06 PM
Second Plumbing Review: COMMENT 1 REMAINS
Unresolved-1). Plan Page A1.3: Missing Lavatory Fixture spacing Measurements. Add Lavatory Fixture spacing
Measurements.. -2018 IPC 405.3.1**NOW THAT LAVATORY MEASURMENTS HAVE BEEN PROVIDED, LAVS NEED 30"
MINIMUM SEPARATION FROM EACH OTHER CENTER TO CENTER**
RESOLVED-2). Plan Page P1.1.1: Indirect waste piping that exceeds distances listed in -2018 IPC 802.3 shall be trapped.
Update detail #2 to comply with -2018 IPC 802.3
RESOLVED-3). Plan page P1.3 : Water piping to H201 (oven) needs backflow protection. Add Backflow protection device to
H201 oven water connection -2018 IPC 608.3
RESOLVED-4). Plan Page P1.2: Water riser missing the H201 oven water line. Add the H201 oven water line to the water
riser. -2018 IPC 106.3.1
RESOLVED-5). Plan Page P1.2 grease interceptor load table: The Floor sinks & floor drains can't have a DFU load of zero.
Update the Grease interceptor load table with DFU amounts derived from -2018 IPC section 709 thru 709.4.1
04/08/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0225-00215
5502 E GRANT RD

Site Engineering approval for this permit cannot be granted until the associated development package (DP) -- TD-DEV-0924-00266 -- is issued.
04/10/2025 Site Zoning Standard REQUIRES RESUBMIT Although the plans appear to match, final Site Zoning approval for this permit cannot be granted until the associated development package (DP) -- TD-DEV-0924-00266 -- is issued. Although the DP has received all approval, outstanding pre-issuance conditions remain. Please reach out in case of any questions to fernando.garcia2@tucsonaz.gov.
03/19/2025 PDSD Application Completeness Express REVIEW COMPLETED