Permit Number: TC-COM-0225-00214
Parcel: 141186060

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00214
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/12/2025 7:17:24 PM
1. E5.0: Many detail notes shown but not identified on Detail sketches 1, 2, 2a, 2b, and 2c. Should have provided description notes, referenced drawing where notes are located, or clarification if not critical.
02/20/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 2/18/2025 10:41:21 PM
First Plumbing Review: OK
02/20/2025 Outdoor Lighting Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/12/2025 7:17:24 PM
1. E5.0: Many detail notes shown but not identified on Detail sketches 1, 2, 2a, 2b, and 2c. Should have provided description
notes, referenced drawing where notes are located, or clarification if not critical.
02/26/2025 Site Zoning Standard APPROVED
02/26/2025 Water - PDSD Standard APPROVED
03/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/20/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 2/18/2025 12:18:44 PM
1. SHEET A3.0 - NEW DRIVE THRU CANOPY: Please provide construction documents for the new drive-thru canopy
shown in Architectural Elevations 1 & 2 on Sheet A3.0. Canopies shall be designed per the 2018 International Building
Code, Section 3105. Construction documents must include, at a minimum:
i. Overall dimensions of the canopy
ii. A detail of the canopy anchorage to the building
iii. Wind design criteria, including the design wind pressure used for components and cladding materials (expressed in pounds per square foot) as dictated by the 2018 IBC Section 1603.1.4.5

Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 2/20/2025 12:39:17 AM
02/20/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/17/2025 9:37:10 AM
1. General - Provide Minimum Mechanical Design Criteria. If applicable, provide Mechanical Plans. Show all existing to stay, existing to be relocated, existing to be removed, and new Supply, Return, and Exhaust duct work. Show termination point on all exhaust duct work. - 2015 IECC Section C103.2Information on construction documents - - 2018 IBC – Section [A]107.2.1Information on construction documents
02/06/2025 Fire New Construction Standard REVIEW COMPLETED
02/05/2025 PDSD Application Completeness Express REVIEW COMPLETED
03/04/2025 Site Engineering Standard REVIEW COMPLETED