Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0225-00214
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 2/12/2025 7:17:24 PM 1. E5.0: Many detail notes shown but not identified on Detail sketches 1, 2, 2a, 2b, and 2c. Should have provided description notes, referenced drawing where notes are located, or clarification if not critical. |
||
| 02/20/2025 | Commercial Plumbing Standard | APPROVED | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 2/18/2025 10:41:21 PM First Plumbing Review: OK |
||
| 02/20/2025 | Outdoor Lighting Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 2/12/2025 7:17:24 PM 1. E5.0: Many detail notes shown but not identified on Detail sketches 1, 2, 2a, 2b, and 2c. Should have provided description notes, referenced drawing where notes are located, or clarification if not critical. |
||
| 02/26/2025 | Site Zoning Standard | APPROVED | |||
| 02/26/2025 | Water - PDSD Standard | APPROVED | |||
| 03/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/20/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 2/18/2025 12:18:44 PM 1. SHEET A3.0 - NEW DRIVE THRU CANOPY: Please provide construction documents for the new drive-thru canopy shown in Architectural Elevations 1 & 2 on Sheet A3.0. Canopies shall be designed per the 2018 International Building Code, Section 3105. Construction documents must include, at a minimum: i. Overall dimensions of the canopy ii. A detail of the canopy anchorage to the building iii. Wind design criteria, including the design wind pressure used for components and cladding materials (expressed in pounds per square foot) as dictated by the 2018 IBC Section 1603.1.4.5 Building(B) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 2/20/2025 12:39:17 AM |
||
| 02/20/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 2/17/2025 9:37:10 AM 1. General - Provide Minimum Mechanical Design Criteria. If applicable, provide Mechanical Plans. Show all existing to stay, existing to be relocated, existing to be removed, and new Supply, Return, and Exhaust duct work. Show termination point on all exhaust duct work. - 2015 IECC Section C103.2Information on construction documents - - 2018 IBC – Section [A]107.2.1Information on construction documents |
||
| 02/06/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 02/05/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 03/04/2025 | Site Engineering Standard | REVIEW COMPLETED |