Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0225-00213
Parcel: 13205015V

Address:
3440 E 36TH

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0225-00213
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2025 Commercial Electrical Fast REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00213 (3440 E 36TH TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. There is no record of the existing building or permit history for its installation/construction. Provide the permit number this building was permitted under.
2. If the building needs to be permitted, then you will need to withdraw this permit and submit for a new construction permit and include the electrical installation in that permit.

>>> Clarify if there is any new outdoor lighting fixtures receiving power for the first time.
Outdoor Lighting Review:
1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2 or show the exterior light as full-cutoff and under a canopy or overhang, OLC 401.2.1 item 3.
2. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
3. Submit catalogue or specification sheets of the proposed light fixture illustrating the type of fixture they are whether full cut-off or unshielded.

Contact Jeremy Hamblin with any questions: email: Building_Official@tucsonaz.gov
02/06/2025 PDSD Application Completeness Express REVIEW COMPLETED