Permit Review Detail
Review Status: Approved
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0224-00384
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2024 | External Reviewers - Willdan | APPROVED | Ed Kulik ekulik@willdan.com 1. Sheet A1.0 Will the 1st floor unit be made into Type A Units? Has this been discussed with the COT? It appears you are upgrading the MPE to the current code. 2. Sheet A1.0 Provide a thermal expansion tank at water heater P2903.4.1. 3. Sheet M1.0 Provide a secondary condensate line per M1411.3. 4. Sheet E1.0 Provide GFCI Outlet at Peninsular per E3901.4.3. |
||
| 04/02/2024 | Site Zoning | APPROVED | |||
| 04/01/2024 | Site Engineering | NOT REQUIRED | |||
| 04/02/2024 | Bldg Permits - Post Review Express | REVIEW COMPLETED | |||
| 03/04/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 03/01/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |