Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0224-00381
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2024 | Commercial Building | APPROVED | |||
| 03/14/2024 | Site Zoning | APPROVED | |||
| 03/18/2024 | Site Engineering | NOT REQUIRED | |||
| 03/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/19/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show all replaced electrical outlets and lighting with assigned branch circuits on the electrical floor plan. 2 Provide for Combination AFCI and GFCI protection for branch circuits as required per NEC art 210.8 and 210.12. 3 Branch circuits shall be identified accurately in the panel schedule, Per NEC art 408.4. 4 Provide compliance with the 2012 City of Tucson Outdoor Lighting Code where applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
||