Permit Number: TC-COM-0224-00381
Parcel: 11613228C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0224-00381
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2024 Commercial Building APPROVED
03/14/2024 Site Zoning APPROVED
03/18/2024 Site Engineering NOT REQUIRED
03/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Show all replaced electrical outlets and lighting with assigned branch circuits on the electrical floor plan.

2 Provide for Combination AFCI and GFCI protection for branch circuits as required per NEC art 210.8 and 210.12.

3 Branch circuits shall be identified accurately in the panel schedule, Per NEC art 408.4.

4 Provide compliance with the 2012 City of Tucson Outdoor Lighting Code where applicable.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
03/04/2024 Fire New Construction REVIEW COMPLETED
03/04/2024 PDSD Application Completeness Express REVIEW COMPLETED