Permit Number: TC-COM-0224-00375
Parcel: 10309057A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0224-00375
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/21/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
03/21/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Provide a detail showing how the horizontal flues are to be installed. Show the required clearances from the wall and the minimum total length for the flues. Reference: Section 620.1, IFGC 2018.
2. Provide structural calculations and details to show how the unit heaters are to be connected to the building structure. Reference: Section 620.2, IFGC 2018.
3. Provide a detail showing the mounting height of the unit heaters and the required clearances from combustibles. Reference: Sections 620.4 and 620.5, IFGC 2018.
03/21/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Southwest Gas provides natural gas at 7” WG, 2 PSIG, and 5 PSIG. For a service pressure of 14” WG, state which pressure will be required for the gas delivery from Southwest Gas (i.e. 2 PSIG or 5 PSIG).
2. The specified unit heaters, Dayton Models 55FG70 and 55FG72, use standard combustion, not sealed combustion. Reference: Section 301.3, IFGC 2018.
02/29/2024 PDSD Application Completeness Express REVIEW COMPLETED