Permit Number: TC-COM-0224-00356
Parcel: 110113620

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0224-00356
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2024 Commercial Building APPROVED
03/14/2024 Commercial Electrical APPROVED
03/19/2024 Commercial Plumbing APPROVED
03/06/2024 Site Zoning APPROVED
03/19/2024 Water - PDSD APPROVED
03/08/2024 Site Engineering NOT REQUIRED
03/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/19/2024 Commercial Mechanical REQUIRES RESUBMIT Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted. The exhausted air from the restroom shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
03/05/2024 Fire New Construction REVIEW COMPLETED
02/28/2024 PDSD Application Completeness REVIEW COMPLETED