Permit Number: TC-COM-0224-00353
Parcel: 133224970

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00353
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2024 Commercial Electrical APPROVED
07/12/2024 Commercial Structural APPROVED
07/15/2024 Water - PDSD APPROVED
07/15/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Requested document not submitted. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.]
2. Comment not addressed. [Initial comment: Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.]
3. Condensate drains may not drip onto the roof and may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. [Initial comment: Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.]
4. The ventilation calculations show 1100 CFM of outside air but only 110 CFM continuous exhaust (460 CFM when intermittent exhaust is included). Explain how the pressurization of the building will be handled. Reference: Section 403.1, IMC 2018. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.]
07/15/2024 Commercial Plumbing REQUIRES RESUBMIT Tucson Water will not allow water meters and backflow preventers to be manifolded to achieve additional capacity. A demand of 87 wsfu (approx. 41 GPM) will require a 1” water meter. [Initial comment: Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.]
06/07/2024 PDSD Application Completeness Express REVIEW COMPLETED