Permit Number: TC-COM-0224-00342
Parcel: 133201440

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00342
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/8/2024 12:04:43 PM
1. GENERAL - MECHANICAL LOADS: Dental Equipment Details on Sheets SED.1 thru SED.3 indicate that all new equipment shall be either slab-supported, counter- or wall-mounted. Dental Lights requiring ceiling reinforcement per Sheet SA.1 are understood to weigh less than 100 lb per Detail 6A on Sheet SED.1. No Mechanical Roof Plan has been provided. Therefore, it is the responsibility of the contractor and MEP designer to confirm that no new equipment in excess of 300 lb shall be supported from the roof or ceiling without the consultation of a structural engineer.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 4/23/2024 4:45:38 PM
1. Cover Sheet/Architectural Site Plan: An architectural site plan has not been provided. Provide an architectural site that contains the following: UNRESOLVED
◦ Prepared to an approved architectural or engineering scale (see above requirements).
◦ Show the property boundary lines.
◦ Placement of all existing buildings or structures on the property, with an assumed or imaginary property line between structures to establish fire separation distances and fire resistance rating requirements within the adopted edition of the International Building Code.
◦ The Accessible Route/Exit Discharge Plan or information is provided to show the running slopes and cross slopes for verification of compliance with the 2010 ADA Standards for Accessible Design and the means of egress requirements of the 2018 IBC.

◦ NOTE: Site plan not provided. Provide a detailed site plan.

2. General: No existing plan has been provided. Provide a detailed existing conditions plan. RESOLVED

3. General: No demolition plan has been provided. Provide a detailed demolition plan. RESOLVED

4. Sheet A4/Door Schedule: The door for the med gas room is not rated properly. Provide a properly rated med gas room door in accordance with 2018 IBC Section 427.2.2. UNRESOLVED

◦ NOTE: The updated drawing referenced in the comment letter has not been provided. Provide the referenced updated drawing.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/11/2024 12:26:37 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 4/23/2024 5:36:18 PM
1. Comment: “Need to provide interior lighting comcheck or hand calculation to show 2018 IECC compliance”.

Response: The 2018 IECC compliance certificate for interior lighting has been provided. Unresolved, no 2018 IECC comcheck provided, only light fixture cutsheets.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 4/28/2024 6:49:18 PM
Second Plumbing Review:OK
Resolved-1). General: Building plan review comments 2 & 4 need to be addressed. -2018 IPC 106.3.1

2). The piping materials for sanitary, water, compressed air, med gas, & vacuum are missing from plan page P7, On plan page P7 please add a piping/fitting materials schedule according to -2018 IPC 605.4, 702, NFPA99

Resolved-3). The required med Gas room door sign verbiage is missing, add this information to plan page A4's door schedule according to -2018 NFPA99 5.1.3.1.9
04/25/2024 Fire New Construction REVIEW COMPLETED
04/23/2024 PDSD Application Completeness Express REVIEW COMPLETED