Permit Number: TC-COM-0224-00342
Parcel: 133201440

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0224-00342
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
05/17/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/8/2024 12:04:43 PM
1. GENERAL - MECHANICAL LOADS: Dental Equipment Details on Sheets SED.1 thru SED.3 indicate that all new equipment shall be either slab-supported, counter- or wall-mounted. Dental Lights requiring ceiling reinforcement per Sheet SA.1 are understood to weigh less than 100 lb per Detail 6A on Sheet SED.1. No Mechanical Roof Plan has been provided. Therefore, it is the responsibility of the contractor and MEP designer to confirm that no new equipment in excess of 300 lb shall be supported from the roof or ceiling without the consultation of a structural engineer.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 4/24/2024 10:43:49 AM


Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/11/2024 12:26:37 PM



Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/10/2024 10:58:46 PM


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 4/28/2024 6:49:18 PM
Second Plumbing Review:OK
Resolved-1). General: Building plan review comments 2 & 4 need to be addressed. -2018 IPC 106.3.1

2). The piping materials for sanitary, water, compressed air, med gas, & vacuum are missing from plan page P7, On plan page P7 please add a piping/fitting materials schedule according to -2018 IPC 605.4, 702, NFPA99

Resolved-3). The required med Gas room door sign verbiage is missing, add this information to plan page A4's door schedule according to -2018 NFPA99 5.1.3.1.9
05/13/2024 PDSD Application Completeness Express REVIEW COMPLETED