Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/28/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/28/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Sheet 23-1595-A/23-1595-B: Please provide evidence and basis for the note #7. 6" Thick/4000 psi concrete. IBC 107.2.1 2. Further, related to above note, provide the geotechnical report indicating the soil bearing pressure. IBC 107.2.1 3. Sheet 23-1595-B: Please update code reference in note #1 to reflect 2018 IBC as amended by the City of Tucson. IBC 107.2.1 4. Sheet 23-1595-A/23-1595-B: Please amend plans to provide Load Plaque. Clarify that signage will be posted clarifying allowable loads per type of storage rack. as required by ANSI MH16.1, Section 4.5 Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
03/19/2024 | Fire New Construction | REVIEW COMPLETED | |||
03/13/2024 | PDSD Application Completeness | REVIEW COMPLETED |