Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0224-00334
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/26/2024 | Water - PDSD | APPROVED | |||
03/26/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/04/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 3/3/2024 6:35:33 AM 1. Structural calculation shows occupancy group as “M Mercantile” while Sheet G1.0 shows as “Assembly group A-2. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 3/3/2024 6:36:36 AM 1. Sheet G1.0 – Applicable codes years do not match in the documents. “IBC 2021” and “IPC 2021” are referenced but 2018 applies at City of Tucson. Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 3/3/2024 6:36:06 AM 1. COMcheck is using 2021 IECC not 2018. Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 3/3/2024 6:36:21 AM 1. G1.0 – Applicable codes missing “City of Tucson/Pima County Outdoor Lighting Code. Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 3/3/2024 6:35:50 AM 1. Sheet P5.1 – Grease interceptor sizing designer for “Phoenix” while this is City of Tucson/Pima County application. Design per 2018 IPC City of Tucson code amendments section 1003.3 (Grease interceptors). |
||
03/18/2024 | Fire New Construction | REQUIRES RESUBMIT | -Clarify fire sprinkler and fire alarm. Sheet G0.0 states fire sprinklers and fire alarm will be deferred submittals which indicates they will be installed. Sheet G1.0, code analysis, states "NA" for fire sprinklers under use and occupancy classification. This sheet also states fire alarm for deferred submittals. john.vincent@tucsonaz.gov 5203495581 |
||
03/18/2024 | Site Engineering | REQUIRES RESUBMIT | 1. The building permit cannot be approved until the associated development package, TD-DEV-1123-00451, has been approved. Lianne Evans lianne.evans@tucsonaz.gov |
||
03/21/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: Wyatt Berger Lead Planner PROJECT: TC-COM-0224-00334 10048 East Old Vail Road – PAD-36 New Food Service building (1st Review) TRANSMITTAL DATE: March 21, 2024 Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed. 1. Zoning has reviewed the building plans for compliance with the associated development package TD-DEV-1123-00451. Although it appears the building plan footprint, building height, and square footage are consistent with the submitted DP, Zoning cannot approve TC-COM-0224-00334 until the development package has been approved by all reviewers. 2. Any civil drawings included within the building plans should either be removed from the plan set or be marked “REFERENCE ONLY.” If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951. |
||
02/26/2024 | PDSD Application Completeness | REVIEW COMPLETED |