Permit Number: TC-COM-0224-00334
Parcel: 141186510

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00334
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2024 Water - PDSD APPROVED
03/26/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/04/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 3/3/2024 6:35:33 AM
1. Structural calculation shows occupancy group as “M Mercantile” while Sheet G1.0 shows as “Assembly group A-2.



Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 3/3/2024 6:36:36 AM
1. Sheet G1.0 – Applicable codes years do not match in the documents. “IBC 2021” and “IPC 2021” are referenced but 2018 applies at City of Tucson.



Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 3/3/2024 6:36:06 AM
1. COMcheck is using 2021 IECC not 2018.



Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 3/3/2024 6:36:21 AM
1. G1.0 – Applicable codes missing “City of Tucson/Pima County Outdoor Lighting Code.



Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 3/3/2024 6:35:50 AM
1. Sheet P5.1 – Grease interceptor sizing designer for “Phoenix” while this is City of Tucson/Pima County application. Design per 2018 IPC City of Tucson code amendments section 1003.3 (Grease interceptors).
03/18/2024 Fire New Construction REQUIRES RESUBMIT -Clarify fire sprinkler and fire alarm. Sheet G0.0 states fire sprinklers and fire alarm will be deferred submittals which indicates they will be installed. Sheet G1.0, code analysis, states "NA" for fire sprinklers under use and occupancy classification. This sheet also states fire alarm for deferred submittals.
john.vincent@tucsonaz.gov
5203495581
03/18/2024 Site Engineering REQUIRES RESUBMIT 1. The building permit cannot be approved until the associated development package, TD-DEV-1123-00451, has been approved.

Lianne Evans
lianne.evans@tucsonaz.gov
03/21/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-COM-0224-00334
10048 East Old Vail Road – PAD-36
New Food Service building (1st Review)

TRANSMITTAL DATE: March 21, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with the associated development package TD-DEV-1123-00451. Although it appears the building plan footprint, building height, and square footage are consistent with the submitted DP, Zoning cannot approve TC-COM-0224-00334 until the development package has been approved by all reviewers.

2. Any civil drawings included within the building plans should either be removed from the plan set or be marked “REFERENCE ONLY.”

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/26/2024 PDSD Application Completeness REVIEW COMPLETED