Permit Number: TC-COM-0224-00323
Parcel: 11104221A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00323
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2024 Commercial Mechanical APPROVED
03/04/2024 Site Zoning APPROVED
03/26/2024 Water - PDSD APPROVED
03/12/2024 Site Engineering NOT REQUIRED
03/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/25/2024 Commercial Electrical REQUIRES RESUBMIT Ref; Plan sheet E3.0.

1 Indicate OCPD rating for the WH-1 in the panel schedule.

2 The load conductors cannot be located in the same enclosure (Bussed Gutter) as service conductors, NEC 230.7.

3 Are the main service disconnects fused? Indicate fuse types and ratings.

4 Ref; E2.1 and E3.0. The Electric Feeder Schedule shows a ‘HOOD EF’ equipment that is not shown in the panel schedules or Mechanical Power Plan. Please clarify.

REf; 2018 IBC section 107.2.1, 2017 NEC
03/26/2024 Commercial Plumbing REQUIRES RESUBMIT The specified waterless urinal does not require an external trap, just a urinal flange. (Note: the specified model of the urinal has been discontinued by the manufacturer.) Reference: Sections 303.2 and 1002.1, IPC 2018.
03/28/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Sheet A1: Please amend General Notes #1 to include IECC, IEBC, 2009 ICC A117.1 Accessibility Code (by reference) and, add “As amended by the City of Tucson.”
2. Sheet A3: Please amend plans to show the locations of Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs.
3. Sheet A4: Please provide dimensions to indicate the width of all openings and doorways. IBC 107.2.3
4. 2. Sheet A4: Please provide drawings and details to indicate how New Wall are to be constructed. IBC 107.2.1
5. Sheet A4: Please amend plans to provide a 60-inch clearance in minimum width around the water closet without the urinal within the required water closet clearance. The 60-inch requirement provides approximately 30 inches between the water closet and the nearest wall or fixture. This space allows the wheelchair user to back into the space and accomplish a side transfer from the wheelchair to the water closet. 2009 ICC A117.1 604.3.1& 604.3.3.
6. Sheet A4: Please amend plans to provide the required clear floor space of 36” for the bathroom lavatory set in an alcove. Where the clear floor space is positioned for a forward approach, the alcove shall be 36 inches minimum in width where the depth exceeds 24 inches. ❖ The normal 30-inch width of a clear floor space must be increased to 36 inches when any type of obstruction occurs on all or part of three sides and the clear floor space extends more than 24 inches into the confined area. 2009 ICC A117.1 305.7.2

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
03/13/2024 Fire New Construction REVIEW COMPLETED
02/26/2024 PDSD Application Completeness Express REVIEW COMPLETED