Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0224-00323
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/14/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show the locations of the ‘K20’ exterior luminaires. 2 Indicate fuse sizes and types for the service disconnects. 3 Provide for gas piping, building steel bonding to the electrical service GES if applicable. NEC 250.104. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 05/16/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Please remove the urinal from the waste isometric, A/P2. [Initial comment: The specified waterless urinal does not require an external trap, just a urinal flange. (Note: the specified model of the urinal has been discontinued by the manufacturer.) Reference: Sections 303.2 and 1002.1, IPC 2018.] | ||
| 05/17/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 3. Sheet A4: Please provide dimensions to indicate the width of all openings and doorways. IBC 107.2.3 This comment was satisfied with one exception, the doorway between storage area near the (E) Walk In and the Retail area. It appears to be undersized, as the minimum clear width is 32". IBC 1010.1.1 Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
| 04/16/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |