Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0224-00319
Parcel: 11014015A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0224-00319
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2024 Water - PDSD APPROVED
03/07/2024 Site Engineering NOT REQUIRED
03/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/13/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.

1. Please amend plans to indicate the location of the new light pole as shown on sheet E1. IBC 107.2.1
2. Further, related to above comment, please provide structural calculations for the new light pole and foundation IBC 107.2.7
Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
03/12/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Please provide full compliance with the 2012 City of Tucson Outdoor Lighting Code for the new exterior luminaires.

2 Why is there 2 Lighting Fixture Schedules, and where is the ‘A1’ luminaire(s) located?

3 Why is plan sheet ‘E1’ addressed at 2505 E 36th st.? Please clarify.

Ref; 2018 IBC section 107 2 1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
03/19/2024 Commercial Mechanical REQUIRES RESUBMIT Footnote g, Table 403.3.1.1, IMC 2018, calls for public restrooms to be mechanically exhausted. Show how this will be provided for the new restroom. Reference: Section 403.2.1 (4), IMC 2018.
03/19/2024 Commercial Plumbing REQUIRES RESUBMIT Provide a cleanout at the junction of the building drain and the building sewer. Reference: Section 708.1.3, IPC 2018.
03/05/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0224-00319
2900 N CRAYCROFT RD. – HRX-2
Remodel existing restroom (1st Review)

TRANSMITTAL DATE:‎ March 5, 2024

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: the following comments are relative to an application for Historic Review (UD5.8.8). This site is located in the HRX-2 zone (UDC 4.7.7). Parks and Recreation is an allowed use in the zone (UDC Table 4.8-1), subject to Use Specific Standards 4.9.13.B & C.

1. Until approved by Historic Zoning cannot approve this plan. Historic Review is required. Please submit a special districts application as a sub-record of this permit. The submittal requirements and instructions can be found below. Please contact Jodie Brown (jodie.brown@tucsonaz.gov) or Michael Taku (michael.taku@tucsonaz.gov) for any questions. Zoning can not approve until the historic review has been approved. https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/planning-amp-zoning/special_districts_application_instructions-1.pdf

2. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/26/2024 Fire New Construction REVIEW COMPLETED
02/26/2024 PDSD Application Completeness Express REVIEW COMPLETED