Permit Number: TC-COM-0224-00308
Parcel: 10604308A

Address:
3233 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4

Permit Number - TC-COM-0224-00308
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The 2017 NEC requires 1 electrical service per building on the premises per article 230.2. Provide for a single service drop utilizing a 3 or 4 -meter pack type service equipment.

2 Verify or show the location of the subpanels in the buildings to verify compliance with NEC article 240.24(D)(E), and 408.17. (Not located in closets or bathrooms).

3 Provide complete panel schedules. Show amp rating of the equipment and load calculations.

Be advised that there is always the option to file an appeal to the Building Official for a code variance associated with NEC article 230.2. This is an online process through the PDSD website.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
06/18/2024 PDSD Application Completeness Express REVIEW COMPLETED