Permit Number - TC-COM-0224-00308
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/02/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The 2017 NEC requires 1 electrical service per building on the premises per article 230.2. Provide for a single service drop utilizing a 3 or 4 -meter pack type service equipment. 2 Verify or show the location of the subpanels in the buildings to verify compliance with NEC article 240.24(D)(E), and 408.17. (Not located in closets or bathrooms). 3 Provide complete panel schedules. Show amp rating of the equipment and load calculations. Be advised that there is always the option to file an appeal to the Building Official for a code variance associated with NEC article 230.2. This is an online process through the PDSD website. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||